西门子C7-634 DP面板(OP17)串口连接线接线图

西门子面板C7-634 DP (OP17) 用ProTool下载数据时,需要串口连接电缆,但是该面板是15针母头D型接口,而电脑上串口是9针公头D型接口。那么15针和9针两者针脚是如何对应连线的呢?LT 对此作了笔记。

在网上搜索资料如下:http://www.plctalk.net/qanda/showthread.php?t=9115

I have cable of Siemens 6XV1440-2KH32 at my eyes. There are two side: 1-(for serial 9 pin) and another 2-(15 pin for OP).
9pin—————————————-15pin
1+4+6(are connected)
7+8(are connected)
2——————————————-4
3——————————————-3
5——————————————-12

在西门子网站上找到此电缆 6XV1440-2K___ 官方接线图 (链接link

相关文章:

  • S7 300 and OP7 (E4027: Synchronization faulty)
    http://www.plctalk.net/qanda/showthread.php?t=24058
  • What connecting cables are there for connections between the operator panels and the different controllers?
    http://support.automation.siemens.com/WW/llisapi.dll?func=cslib.csinfo&lang=en&objid=29034071&caller=view
  • 面板上传下载问题集(ProTool)(更新版)文档编号 A0110 日期2008/01/15
    http://www2.ad.siemens.com.cn/Download/Upload/AS/application/A0110.pdf
  • OP7, OP17 Operator Panel Equipment Manual http://support.automation.siemens.com/WW/view/en/1145112